Xiamen Xingruijia Import and Export Co., Ltd. has been specializing in the sales of industrial control equipment spare parts for 20 years. For more ABB models, please refer to the product list . If you need other brands or models, please contact us. We have a variety of brands and models in stock, and we can purchase difficult to order models for you. We look forward to your inquiry!!!
First hand source//affordable price//Spot inventory!
•Shipping Port: Xiamen
•Manager: Rhonda
•E-mail: sales7@saulplc.com
•Tel/WhatsApp/Wechat: + 86-15359273796
•Ship to you via Fedex/DHL/TNT/UPS/EMS
•Package: Original packing with cartons
==============================================================================================================================================
ABB 3BSE028586R1 DI880
ABB DI880 (3BSE028586R1) is a High Integrity Digital Input Module from the ABB S800 I/O family, designed for safety-critical process automation applications. It provides 16-channel 24 V DC digital inputs and supports both single and redundant configurations.
1. General Information
| Item |
Description |
| Manufacturer |
ABB |
| Product type |
Digital Input Module |
| Model |
DI880 |
| Article number |
3BSE028586R1 |
| Series |
ABB S800 I/O / System 800xA |
| Signal type |
24 V DC digital input |
| Channels |
16 |
| Configuration |
Single or redundant |
| Safety level |
High Integrity, SIL3 certified |
| HART support |
No |
| SOE (Sequence of Events) |
Yes |
| Intrinsic safety |
No |
| |
|
2. Technical Specifications
| Parameter |
Specification |
| Input voltage range |
18–30 V DC |
| Input current |
Approx. 7 mA at 24 V DC |
| Input type |
Current sinking |
| Input impedance |
3.1 kΩ |
| Isolation |
Groupwise isolated from ground |
| Digital filter time |
Adjustable 0–127 ms |
| Maximum cable length |
Up to 600 m |
| Power dissipation |
Approx. 2.4 W |
| ModuleBus current consumption |
125 mA typical / 150 mA max at +5 V |
| External 24 V consumption |
15 mA + sensor power (max. 527 mA) |
| |
|
3. Key Features
- 16 independent 24 V DC input channels
- High-integrity safety design
- Supports redundant operation
- SIL3 certification according to IEC 61508
- Category 4 capability according to EN 954-1
- Built-in input status LEDs
- Advanced onboard diagnostics
- Optical isolation and EMC protection
- Current-limited sensor supply for each input
- Sequence of Events (SOE) recording with 1 ms resolution
4. SOE Function (Sequence of Events)
The DI880 includes a high-speed event recording function suitable for safety and trip analysis:
- Event resolution: 1 ms
- Event accuracy: -0 ms / +1.3 ms
- Event queue capacity: 512 × 16 events
- Supports event filtering (shutter filter)
- Reports channel status, queue status, synchronization jitter, uncertain time, and channel errors
5. Diagnostics and Indicators
Front panel indicators include:
- Fault (F)
- Run (R)
- Warning (W)
- Primary (P)
- Channel status LEDs (1–16)
Diagnostic monitoring includes:
- Process power supervision
- Internal circuit monitoring
- Module errors
- Channel errors
- Warning status
6. Compatible Module Termination Units (MTU)
The DI880 can be used with ABB S800 I/O MTUs including:
- TU810
- TU812
- TU814
- TU818
- TU830
- TU833
- TU838
- TU842
- TU843
- TU852
7. Mechanical Data
| Parameter |
Value |
| Width |
45 mm |
| Height |
119 mm |
| Depth |
102 mm (111 mm including connector) |
| Protection class |
IP20 |
| Weight |
Approx. 0.15–0.25 kg |
| |
|
8. Typical Applications
ABB DI880 is commonly used in:
- Safety Instrumented Systems (SIS)
- Emergency shutdown systems (ESD)
- Burner management systems
- Turbine and power plant protection
- Oil & gas process safety systems
- Chemical and petrochemical plants
- High-availability industrial automation systems
Conclusion
The ABB DI880 3BSE028586R1 is a SIL3-rated high-integrity 16-channel 24 V DC digital input module for ABB S800 I/O and System 800xA environments. Its combination of redundancy support, SOE capability, diagnostics, and safety certification makes it suitable for critical protection and process-control applications where reliable signal acquisition is required.